When fire sprinkler systems activate and/or release water we are frequently retained to determine if the systems worked as intended. In the course of these investigations there are common questions that need to be addressed involving system design, maintenance and inspection. This article provides a starting point for fire sprinkler system investigations.

Although there are other types of extinguishing agents, fire sprinkler systems most often rely on water to extinguish a fire. Water is delivered through an engineered system of piping to automatic sprinklers that open in response to a fire.
Water is typically supplied to the sprinkler system from the municipal water supply. When the water supply is inadequate a fire pump is used to boost the flow and pressure to the sprinkler system. When a municipal water supply is not available a storage tank can be used. In all cases, there must be a sufficient amount of water flow and water pressure available at the time of a fire for the sprinkler system to do its job and put out the fire.
Questions to ask related to the water supply include:
Automatic fire sprinklers are designed to open in response to the heat from a fire. Sprinklers with fusible metal elements employ an alloy engineered to melt at a specific temperature. Glass bulb sprinklers contain a liquid that expands and shatters the bulb at a predetermined temperature. Common activation temperatures are 135°F, 155°F, 175°F and 200°F.
If sprinklers with higher temperature ratings are used in a system designed for lower temperature sprinklers, activation can be delayed until the fire is larger. This can cause more sprinklers to open and the system may not be able to deliver enough water to extinguish the fire.
On the other hand, if a sprinkler with too low a temperature rating is used, it can cause the sprinkler to open when no fire has occurred. An example of this is a warehouse area with high ceilings where the summertime temperature at the ceiling may be hot enough to activate a low temperature sprinkler, or a Server/IT Room where the heat load from the IT equipment may be hot enough to activate a low temperature sprinkler.
Deflectors attached to sprinklers direct the water in the proper direction once they open. Sidewall sprinklers have deflectors that direct the water in a semicircle away from the wall while ceiling sprinkler deflectors direct the water in more of a circle. If a sidewall sprinkler is used in a ceiling application, water will be directed only in one direction and may not reach the entire fire area.
Questions to ask related to sprinklers include:
The most common type of sprinkler system is a wet system. Wet systems have water under pressure in the piping at all times. However, wet systems cannot be used in unheated spaces since the water can freeze and prevent the system from operating in a fire or cause the piping to burst.
Dry systems are designed to be used in areas of buildings subject to freezing. Dry systems contain air under pressure in the piping. When a sprinkler opens in response to a fire, the air is discharged and water can enter and be delivered to the fire. Since dry system piping contains only air it cannot freeze.
Questions to ask related to the system type include:
National Fire Protection Association (NFPA) Standard 25, Standard for the Inspection, Testing and Maintenance of Water Based Fire Protection Systems contains requirements intended to keep sprinkler systems in good repair.
The standard covers periodic inspection and testing requirements for both wet and dry systems. The standard requires tags on the system and reports to document compliance.
Questions to ask related to inspection, testing and maintenance include:
In a building with a wet sprinkler system, it is important that all parts of the system be kept above freezing. If areas of the building are left unheated or if the piping is exposed to cold temperatures as a result of leaky construction or improper insulation, the water in the piping can freeze causing the pipe to burst. In such cases significant water damage can result.
Questions to ask related to heating and insulation include:
Fire sprinkler systems are required to be connected to the building fire alarm system. Many building fire alarm systems are monitored and connected to a remote central station alarm service that automatically contacts the fire department in the event of an alarm.
When this type of system is installed, system water flow, valve position, fire pump operation, dry system air pressure and other system information can be monitored. Logs from the monitoring service can be helpful when investigating an incident. It is important to request these logs in a timely manner since the retained log history is often limited.
Questions to ask related to the alarm and monitoring system include:
The mechanical engineers at Robson Forensic are Licensed Professional Engineers who have extensive hands-on experience in fire suppression systems and equipment including wet pipe, dry pipe, residential, pre-action, deluge, standpipe systems and fire pumps. Our experts have extensive experience in residential, commercial, institutional and industrial equipment and building systems.